A carbon bed is sized, not bought. Three numbers on a data sheet do not describe how it will behave in a running booth. |
Face area and the resulting face velocity; carbon grade, usually expressed as an iodine value or CTC number; bed depth and the pressure drop at clean and at final resistance; and the replacement interval. They are one system. Change one and the other three move.
It is the delivered air volume divided by the face area. If the air volume changes — or if filter loading reduces the volume the fans actually deliver — the velocity changes with it. Too high and the contact time is too short for the solvent to be adsorbed. Ask for the velocity at design airflow, not a nominal cabinet dimension.
It tells you how much the carbon can hold, not how long it will last in your booth. Service life depends on solvent load, running hours, humidity, inlet concentration and the face velocity. A higher grade does not by itself justify a longer interval; ask for the basis on which the interval was calculated.
As filters load, the fan works against a higher pressure drop, delivered air volume falls, and the whole airflow calculation shifts — including the face velocity through the carbon. Ask that fan duty and air volume are stated at final resistance, not with clean filters only. This is also why the carbon bed, the fan and the filter stages must be specified together rather than as separate line items.
Solvent adsorption is exothermic. A temperature probe in each cabinet, with an alarm, is a design feature rather than an accessory. And the consumables list must state changes per year and the quantity per change — and it must agree with the specification table. Two different replacement figures in two documents is the most common error in a spare-parts quotation.
|
Figure |
What it controls |
What to put in the spec |
|
Face velocity |
Contact time and adsorption efficiency |
A value at design airflow, with the face area |
|
Carbon grade (iodine / CTC) |
Holding capacity, not service life |
The grade and the test method |
|
Pressure drop, clean and final |
Fan duty, delivered air volume, real face velocity |
Both values, and the fan duty at final resistance |
|
Replacement interval |
Consumables cost and maintenance plan |
Changes per year and quantity per change |
|
Temperature probe |
Early warning of bed overheating |
One per cabinet, with alarm setpoint |
· Quoting a cabinet size instead of a face velocity.
· Treating a higher iodine value as a longer service life.
· Stating fan duty with clean filters only.
· Letting the spare-parts list disagree with the specification table.
· Counting replacement by calendar alone, with no monitoring.
|
The bed, the fan and the filters are one calculation. Specify them as one. |
Send us your specification and we will work through it line by line.
|
A carbon bed is sized, not bought. Three numbers on a data sheet do not describe how it will behave in a running booth. |
Face area and the resulting face velocity; carbon grade, usually expressed as an iodine value or CTC number; bed depth and the pressure drop at clean and at final resistance; and the replacement interval. They are one system. Change one and the other three move.
It is the delivered air volume divided by the face area. If the air volume changes — or if filter loading reduces the volume the fans actually deliver — the velocity changes with it. Too high and the contact time is too short for the solvent to be adsorbed. Ask for the velocity at design airflow, not a nominal cabinet dimension.
It tells you how much the carbon can hold, not how long it will last in your booth. Service life depends on solvent load, running hours, humidity, inlet concentration and the face velocity. A higher grade does not by itself justify a longer interval; ask for the basis on which the interval was calculated.
As filters load, the fan works against a higher pressure drop, delivered air volume falls, and the whole airflow calculation shifts — including the face velocity through the carbon. Ask that fan duty and air volume are stated at final resistance, not with clean filters only. This is also why the carbon bed, the fan and the filter stages must be specified together rather than as separate line items.
Solvent adsorption is exothermic. A temperature probe in each cabinet, with an alarm, is a design feature rather than an accessory. And the consumables list must state changes per year and the quantity per change — and it must agree with the specification table. Two different replacement figures in two documents is the most common error in a spare-parts quotation.
|
Figure |
What it controls |
What to put in the spec |
|
Face velocity |
Contact time and adsorption efficiency |
A value at design airflow, with the face area |
|
Carbon grade (iodine / CTC) |
Holding capacity, not service life |
The grade and the test method |
|
Pressure drop, clean and final |
Fan duty, delivered air volume, real face velocity |
Both values, and the fan duty at final resistance |
|
Replacement interval |
Consumables cost and maintenance plan |
Changes per year and quantity per change |
|
Temperature probe |
Early warning of bed overheating |
One per cabinet, with alarm setpoint |
· Quoting a cabinet size instead of a face velocity.
· Treating a higher iodine value as a longer service life.
· Stating fan duty with clean filters only.
· Letting the spare-parts list disagree with the specification table.
· Counting replacement by calendar alone, with no monitoring.
|
The bed, the fan and the filters are one calculation. Specify them as one. |
Send us your specification and we will work through it line by line.